The cable itself carries no Ex certificate. In a Zone 1 intrinsically safe loop, the Ex ia status belongs to the circuit: the source or barrier, every device on the spur, the cable's electrical parameters, and the installation executed to IEC 60079-14. What you buy from a cable supplier is therefore not a "certified cable" but a documented set of electrical and material parameters that lets you prove the circuit stays inside its limits over your actual run length — plus, if you order terminated assemblies, a separate answer about which certificate covers the assembly and under which scheme. That distinction is the whole RFQ. A datasheet that says "ATEX cable" and stops there tells you nothing you can calculate with. This checklist is the sequence a specifying engineer can hand to a supplier, in order, before releasing an enquiry.
Why the "ATEX cable" framing fails at specification review
Ethernet-APL is a physical layer built for process field conditions, carrying 10BASE-T1L as standardised in IEEE 802.3cg; intrinsic safety is designed into the definition rather than bolted on afterwards, with the 2-wire intrinsically safe Ethernet case addressed by IEC 60079-47:2021 (2-WISE) — as described in Pepperl+Fuchs' October 2023 write-up on implementing 2-WISE intrinsic safety (blog.pepperl-fuchs.com, 4 October 2023). That article also makes the practical point: the relevant installation specifications per IEC 60079-14 and the applicable national or regional regulations govern the installation, and the user's obligation is to select and connect devices suited to the hazardous area and to document the installation and later changes so that compliance with the required limit values is demonstrated. Two procurement consequences follow, and they are the reason this page exists rather than another "what is APL" explainer:
- Ask for parameters and methods, not for a certificate on the reel. Capacitance and inductance per unit length, with the test method and frequency; conductor and shield construction; jacket compound with cited test standards. Those are the inputs to your loop calculation.
- Ask separately about the assembly. If you buy M12-terminated spurs, the question "is this assembly certified, under which scheme and with what scope" is a different question from "what are the cable's electrical values". Mixing the two in one enquiry is how scopes get assumed rather than confirmed.
The approvals landscape is scope-dependent — ATEX, IECEx and NEC505 for Zones 0, 1 and 2, and NEC500 for Divisions 1 and 2, again per the Pepperl+Fuchs article. State the scheme you need on the enquiry. A supplier answering a different scheme's question gives you an answer you cannot compare.
Check 1–2: Lock the area classification and EPL into the enquiry
Zone definitions drive everything downstream, so restate them on the enquiry rather than leaving them to the supplier's assumption. In the widely used IEC/ATEX framing, Zone 0 is an area where an explosive atmosphere is present continuously or for long periods, Zone 1 where it is likely to occur during normal operation, and Zone 2 where it is unlikely in normal operation (see HELU's hazardous-area cable explainer for a published table of these definitions). Your site's classified area drawing — not a blog table — is the governing document. Then require the protection concept, gas group and equipment protection level in writing. A marking such as "Ex ia IIC Gb" or "Ex e IIC Gb" encodes the protection concept, the gas group and the zone suitability; a cable or assembly description that omits the group letter is not a specification, it is a category. Declare the trunk/spur split, because the protection concepts differ by segment. The Ethernet-APL Engineering Guideline v1.11 (Karl-Heinz Niemann, 6 December 2021) describes a reference topology in which the powered trunk is classified increased safety Ex eb / AEx eb for Zone 1 and the spurs are classified intrinsically safe Ex ia for Zone 1/0. Treat that as the guideline's description of a reference topology — not a universal rule. The certified control drawing for your barrier and field switch governs your segment, and the guideline itself notes that devices must be certified for the intended hazardous area location.
Check 3–4: Which sheath and construction claims are worth paying for
Jacket colour is a convention, not a legal requirement
A blue jacket on intrinsically safe circuits is an installation and identification convention in many plants. It is not, on its own, a legal requirement — and it is not evidence of anything. Check your site's marking and identification policy before accepting a colour premium or a long lead time justified by colour. If your plant standard says blue, specify blue; if it does not, "blue for IS" is a supplier talking point.
Demand the compound by name and the test standards by clause
"Oil resistant", "flame retardant" and "chemical resistant" are unusable at specification review without a referenced method and acceptance criterion. Ask for the jacket compound by its material designation and its property data, and for each claim the standard and clause it was tested to: flame propagation, oil and fuel resistance, chemical resistance, UV/weathering, low-temperature flexibility, abrasion. Then match chemical resistance to the actual medium and wash-down regime in your plant. A pharmaceutical wash-down area and an oil-and-gas pump house do not pose the same question, and a generic resistance claim answers neither. Where the medium matters, ask for the supplier's compatibility statement against the specific fluid list, and note what it does and does not cover.
Temperature class reasoning must be stated, not implied
For Zone 1 runs into the field, the T-rating argument is ambient temperature plus conductor temperature rise, compared against the temperature class. A cable datasheet quoting only a 20 °C property does not support that argument. Ask for the cable's temperature data at the installed operating condition and the basis on which it was derived.
Separate engineering requirements from procurement choices
| Requirement type | Examples | What to do |
|---|---|---|
| Engineering requirement | Core geometry, shield construction, capacitance and inductance per unit length and their stability | Must be in the datasheet with a test method; feeds the loop calculation |
| Case-specific requirement | Chemical resistance to the actual medium, low-temperature flexibility at the installed minimum, temperature data at operating condition | Must be stated against a named method and your stated conditions |
| Procurement choice | Jacket colour, halogen-free, UV grade where not site-mandated | Specify only if your site standard requires it; do not pay for it by default |
Check 5: The Cc/Lc budget — the calculation that sets your run length
This is where a datasheet becomes a decision. Under the entity concept of IEC 60079-11, the permitted cable capacitance is the source or barrier's Co minus the sum of Ci of every device on the segment; the same subtraction applies to inductance:
- Cc (permitted) = Co − ΣCi over all devices on the spur
- Lc (permitted) = Lo − ΣLi over the same devices
- Maximum length = permitted Cc ÷ cable capacitance per unit length (and check the same for Lc; the smaller result governs)
An illustrative calculation — assumptions stated, no measurement performed
Assume, purely for illustration, a source with Co = 80 nF and Lo = 3 mH; three devices on the spur with a combined Ci = 10 nF and combined Li = 0.1 mH; and a cable quoted at 60 pF/m and 1 µH/m.
- Permitted Cc = 80 nF − 10 nF = 70 nF → 70 nF ÷ 60 pF/m ≈ 1,170 m by capacitance
- Permitted Lc = 3 mH − 0.1 mH = 2.9 mH → 2.9 mH ÷ 1 µH/m ≈ 2,900 m by inductance
- Capacitance governs at roughly 1,170 m
These are assumed inputs, not test data.
Substitute your barrier's certified Co/Lo, your actual device Ci/Li values from their certificates, and your cable's tested figures. The arithmetic is trivial; the inputs are the work. Where the budget usually breaks: spurs with several field devices rather than one, capacitance added by connectors and terminal blocks, the gap between a nominal datasheet figure and a batch test figure, and short spurs where a percentage delivery-length tolerance is a larger share of the run than it would be on a long trunk. For the 2-wire Ethernet case, the 2-WISE approach in IEC TS 60079-47 exists to make this comparison tractable across manufacturers — but the segment still has to be documented, and changes and extensions recorded, as the Pepperl+Fuchs article notes. Ask the supplier for capacitance and inductance per unit length with the test frequency and method, and for a calculation run against your length and device count. A generic table is not an answer to your loop.
Check 6–7: Trunk vs spur, power, distance, shielding and bonding
The trunk and the spur are different cables with different jobs: the trunk carries power and data across the segment, the spurs reach the instruments. Specify them separately instead of ordering "APL cable" and letting the supplier choose. On performance figures, attribute them rather than absorb them: the 10 Mbit/s rate and reach of up to 1,000 m are the figures given by industrialethernet.net (20 May 2024) in its overview of single-pair Ethernet in hazardous environments, and the Ethernet-APL Engineering Guideline v1.11 states that length limitations and voltage drop on a powered trunk have to be observed. Neither figure is a promise about your segment — the powered trunk's voltage drop and length calculation sits with your design. Shield construction deserves the same treatment. Ask how the shield is built and where the supplier intends it to be bonded, then check that against your equipotential bonding design. Shield earthing and bonding topology are installation decisions; a cable construction that forces a topology you had not planned becomes a change order late in the project. This is also the point at which termination choice bites: M12-terminated spur assemblies versus field-terminated cable change both the capacitance add-on and the IP rating story. Request the termination and IP claim in writing, per assembly.
Check 8: Marking, test reports and documentation to demand before release
- Cable marking: manufacturer, type, metre marking and batch traceability that ties a delivered reel to the datasheet values.
- Test documentation: which electrical tests were run, on what sample, at what frequency, with what acceptance criteria. A certificate number without the method is not evidence.
- Delivery-length tolerance and how it is measured: it matters more on short spurs than on a long trunk run.
- Certification statement for the assemblies you buy — not for the base cable — per order and per scheme, including the scope of the certificate, not merely its existence.
- Change notification: what the supplier commits to telling you before a compound or construction change. A silent change invalidates the loop calculation you submitted for approval.
The 8-point supplier enquiry checklist
- Area classification, zone, gas/dust group and EPL, plus the certification scheme in scope (ATEX / IECEx / NEC).
- Segment role — trunk or spur — with run length and number of devices per spur.
- Your Co/Lo minus ΣCi/ΣLi budget, or a request for the supplier to compute it against your barrier and device list.
- Capacitance and inductance per unit length with test method and frequency; conductor and shield construction.
- Jacket compound, colour rationale, and the specific test standards claimed for flame, oil, chemical, UV and cold flexibility.
- Temperature data and temperature-class reasoning for the installed condition, not only 20 °C values.
- Termination: M12 assembly or field-terminated, IP rating, and marking/traceability scheme.
- Documentation package: datasheet, test reports, certificate scope, delivery-length tolerance, change-notification commitment.
Questions that come up at review
Does an Ethernet-APL cable need its own ATEX certificate?
Not in the sense the phrase usually implies. The cable is a passive component; the Ex status belongs to the circuit — source or barrier, devices and installation. What the cable must supply is documented electrical and material parameters that let you demonstrate the circuit stays within its limits. The assembly you buy may carry its own certification; that is a separate question with its own scope.
How do I calculate maximum cable length from Cc and Lc for a Zone 1 intrinsically safe loop?
Take the source or barrier's Co and Lo from its certificate, subtract the summed Ci and Li of every device on the spur, then divide each remainder by the cable's per-length capacitance and inductance. The smaller of the two length results governs. Use certified device values and tested cable figures, not catalogue approximations.
Can I use a standard single-pair Ethernet cable for an Ex ia spur in Zone 1?
Only if its published electrical parameters and construction support your loop calculation and your installation requirements, and only if the accessories — connectors, terminations, glands — are suitable for the area. "Standard SPE cable" is a construction description, not a compliance statement; the burden of proof is the calculation plus the installation documentation.
Is a blue sheath mandatory for intrinsically safe circuits in the EU?
Treat blue as an identification convention rather than a legal requirement, and check your site's marking policy. Nothing about the colour changes the circuit's Ex status; the parameters do.
Next step: the datasheet plus your loop calculation
The deliverable worth holding a supplier to is a datasheet with published electrical parameters and a worked budget for your specific loop — not a leaflet with a logo and an approvals strip. Send us your area classification, trunk and spur lengths, device list and the barrier's Co/Lo values. We will return the cable parameters with their test basis and a capacitance/inductance calculation for your loop length and device count, and confirm the certification position for the specific assembly you intend to order — which, for a made-to-order hazardous-area or single-pair Ethernet assembly, is confirmed per order rather than assumed from the cable. For the cable-construction background behind these parameters (cores, shield, jacket build for single-pair Ethernet), see our single-pair Ethernet cable construction article; when you are ready to convert the specification into an order, submit the enquiry through the hazardous-area and single-pair Ethernet assembly quote request and attach the completed 8-point checklist above.
Request the ATEX / IEC 60079 cable datasheet and a capacitance/inductance calculation for your loop length and device count.